Location: the parking area of a new residential building in Hod Hasharon.
Description: this is the fire safety piping and the building's main water supply piping, running along a wall that borders the entrance to the parking garage. The wall has a fall of about 4 m into the ramp below, so a solid, wall-type railing was built to a height of 1.05 m from the floor.
The defect: the piping running parallel to the wall, and the iron guard around it, sit only about 50 cm above the floor and allow climbing. A child can easily climb onto the pipe or the iron guard, then onto the wall, and, heaven forbid, fall into the ramp below, a drop of about 4 m.
The cause: a lack of proper thought at the design stage.
The consequences: a severe safety hazard.
Standard: the defect violates Israeli Standard 1142 for railings, which the contractor is bound to meet.
The repair: remove the ability to climb by boxing in the piping to the height of the railing, or by relocating the railing's route.
Cost of repair: about ₪10,000